      李炳華:IEC電擊防護(hù)標(biāo)準(zhǔn)中4個30mA

      2023/10/21 4:21:40 人評論 次瀏覽 分類:電工基礎(chǔ)  文章地址:http://www.fg316.com/tech/5125.html

      《低壓電氣裝置 第4-41部分:安全防護(hù) 電擊防護(hù)》GB/T 16895.21-2020/IEC 60364-4-41:2017 Low-voltage electrical installations Part  4 – 41:Protection for safety –Protection  against electric shock,4次提到“不超過30mA”RCD的設(shè)置要求,且均為附加防護(hù)!分別如下:

      411.1 通則

      Where specified, additional protection is provided by a residual current protective device (RCD) with rated residual operating current not exceeding 30 mA in accordance with 415.1.

      當(dāng)有具體規(guī)定時,可采用符合415.1條要求的額定剩余電流動作值不超過30mA的剩余電流動作保護(hù)電器(RCD)作附加防護(hù)措施。


      411.3.3 用于插座和戶外移動設(shè)備的供電更進(jìn)一步的要求

      Further requirements for socket-outlets and for the supply of mobile equipment for use outdoors
      Additional protection by means of a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for
      ◆a.c. socket-outlets with a rated current not exceeding 32 A that are liable to be used by ordinary persons and are intended for general use; and
      ◆a.c. mobile equipment for use outdoors with a rated current not exceeding 32 A.

      額定動作電流不超過30mA的剩余電流動作保護(hù)電器(RCD)作為附加防護(hù)用于:

      ①供一般人員用普通用途的額定電流不超過32A的交流插座,和
      ②供戶外額定電流不超過32A的交流移動式設(shè)備。

      411.3.4  在TN和TT系統(tǒng)中用于照明回路的附加要求

      Additional requirements for circuits with luminaires in TN- and TT-systems
      In premises designed to accommodate a single household, additional protection by a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for a.c.final circuits supplying luminaires.

      對于單獨住戶的房屋向照明供電的交流終端回路,應(yīng)提供額定剩余動作電流不超過30mA的剩余電流動作保護(hù)電器(RCD) 作為附加防護(hù)。


      415.1.1  在交流系統(tǒng)內(nèi)裝設(shè)額定剩余電流不大于30mA的RCD,用以在基本防護(hù)失效和/或故障保護(hù)或用電不慎時的附加防護(hù)措施。

      The use of RCDs with a rated residual operating current not exceeding 30 mA, is recognized in a.c. systems as additional protection in the event of failure of the provision for basic protection and/or the provision for fault protection or carelessness by users.

      結(jié)論

      ①擁于保護(hù)人身安全的RCD作為電擊防護(hù)的附加防護(hù)措施,其額定剩余電流動作值都不應(yīng)大于30mA。
      ②國標(biāo)與IEC標(biāo)準(zhǔn)是一脈相承的!